Permit: T09EL01460

Parcel: 13012268A


Addresses:

3650 E MARCH PL

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/25/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/19/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AS PREVIOUSLY NOTED, SMOKE DETECTORS MUST BE AT LEAST 3' FROM COOLER/HEAT REGISTERS
2) WIRES IN LAUNDRY BELOW 8' MUST BE PROTECTED WITH SHEETROCK, PLYWOOD, CONDUIT, ETC...
06/16/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED SMOKE DETECTORS BOTH BEDROOMS AND IN HALLWAY OUTSIDE BEDROOMS AT LEAST 3' FROM REGISTERS AND BETWEEN 6" AND 12" OF CEILING IF WALL MOUNTED
2) BATH AND KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED
3) NEED COVER ON REFRIDGERATOR OUTLET
4) NEED ACCESS TO LAUNDRY/STORAGE ROOM