Permit: T09EL01454

Parcel: 12218122E


Addresses:

1412 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/26/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) #1,4 AND 5 NOT DONE FROM 6/15/09 INSPECTION
2) RECALL WHEN CORRECTIONS ARE COMPLETE AND POWER HAS BEEN RESTORED, FOR FINAL INSPECTION
06/15/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SCREW WATER HEATER VENT PIPE TOGETHER MINIMUM 3 SCREWS AT EACH SEAM
2) KITCHEN COUNTER RECEPTACLE NEEDS GFI PROTECTION
3) BATH RECEPTACLE NEEDS GFI PROTECTION
4) SMOKE DETECTOR REQUIRED IN BEDROOM AT LEAST 3' FROM COOLER REGISTER AND BETWEEN 6" AND 12" OF CEILING IF WALL MOUNTED
5) NEED ADDRESS ON MAIN DISCONNECT SWITCH AT NORTH END OF BLDG