Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T09EL01442
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 06/25/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) #8 GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED IN RACEWAY TO BE PROTECTED FROM PHYSICAL DAMAGE 2) COMPLETELY DRIVE GROUND RODS BELOW GRADE 3) BURY GROUND WIRE TO RODS 4) DEVICE BOXES OVER FILLED |