Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE SMOKE ALARMS WITHIN 36" OF FORCED AIR REGISTERS PER MANUFACTURERS SPECS MUST BE 36" MINIMUM FROM REGISTERS 2) RECALL 2090 |
|
| 06/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL A/C CIRCUIT DEAD FRONT 2) WHITE HOT LEAD MUST BE BLACK OR RED (TAPE) 40 AMP A/C BREAKER 3) SMOKE ALARM BEDROOMS 4) BEDROOM WINDOW BARS MUST OPERATE WITHOUT SEPERATE TOOLS AND DBL KEYED DEAD BOLTS NOT ALLOWED 5) GFCI PROTECT BATH OUTLETS |