Permit: T09EL01421

Parcel: 123172620


Addresses:

1439 E LEE ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01421

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO INSTALL DISCONNECTING MEANS AT BLDG SERVED
2) PLEASE EXPLAIN NEW ROMEX CABLES ENTERING PANEL. ALL NEW WORK REQUIRES PLANS
3) PLEASE VERIFY PERMIT FOR NEW ROOF TOP A/C UNIT
4) ALL NEW SERVICES TO BE UNDERGROUND. NEED TO APPLY FOR OVERHEAD WAIVER. SUB DIVIDING PROPERTY AND BLDG NEW HOME IN BACK. SERVICE BEING INSTALLED ON NEW HOME
5) BOND GAS AND WATER PIPING
6) SEAL OPENING AT WIRE ENTRY WITH NON COMUSTIBLE MATERIAL
7) STRAP GEC TO BLDG SURFACE
8) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL
9) INSTALL FEEDER BREAKER IN SERVICE PANEL
10) USE 1/4" HARDWARE TO FASTEN MAST TO BLDG
07/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR