Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01421
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO INSTALL DISCONNECTING MEANS AT BLDG SERVED 2) PLEASE EXPLAIN NEW ROMEX CABLES ENTERING PANEL. ALL NEW WORK REQUIRES PLANS 3) PLEASE VERIFY PERMIT FOR NEW ROOF TOP A/C UNIT 4) ALL NEW SERVICES TO BE UNDERGROUND. NEED TO APPLY FOR OVERHEAD WAIVER. SUB DIVIDING PROPERTY AND BLDG NEW HOME IN BACK. SERVICE BEING INSTALLED ON NEW HOME 5) BOND GAS AND WATER PIPING 6) SEAL OPENING AT WIRE ENTRY WITH NON COMUSTIBLE MATERIAL 7) STRAP GEC TO BLDG SURFACE 8) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL 9) INSTALL FEEDER BREAKER IN SERVICE PANEL 10) USE 1/4" HARDWARE TO FASTEN MAST TO BLDG |
|
07/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |