Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01399
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/30/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
06/29/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DESCRIPTION OF WORK DOES NOT MATCH ACTUAL INSTALL. THIS IS NEW CIRCUIT FROM SFR TO FEED RECEPTACLE FOR COMMERCIAL MONUMENT ENTRY TO COMMUNITY. WILL ALSO NEED TO PROVIDE APPROVED PLANS 2) NEED TO SUPPORT BELL BOX 3) ROMEX CABLE CANNOT BE INSTALLED IN RACEWAY UNDERGROUND. THIS IS WET LOCATION 4) CANNOT SEE ENTIRE INSTALL BECAUSE HOUSE IS LOCKED UP. NO ONE ON SITE 5) WATT METER NOT LISTED. NO MARKINGS, IF CAN BE USED OUTDOORS |