Permit: T09EL01399

Parcel: 133385210

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01399

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/30/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY CONTRACTOR
06/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DESCRIPTION OF WORK DOES NOT MATCH ACTUAL INSTALL. THIS IS NEW CIRCUIT FROM SFR TO FEED RECEPTACLE FOR COMMERCIAL MONUMENT ENTRY TO COMMUNITY. WILL ALSO NEED TO PROVIDE APPROVED PLANS
2) NEED TO SUPPORT BELL BOX
3) ROMEX CABLE CANNOT BE INSTALLED IN RACEWAY UNDERGROUND. THIS IS WET LOCATION
4) CANNOT SEE ENTIRE INSTALL BECAUSE HOUSE IS LOCKED UP. NO ONE ON SITE
5) WATT METER NOT LISTED. NO MARKINGS, IF CAN BE USED OUTDOORS