Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT AND MINERALLAC STRAP 2. SEPARATE EQUIPMENT GROUNDS AND TERMINATE PER INSTRUCTIONS ON PANEL DOOR 3. NEED CLEARANCE TO SPA PER NEC 680.40 AND 680.8 CHECK WITH TEP FOR CLEARANCE REQUIREMENTS -- THEY MAY REQUIRE 25' CLEARANCE |
|
| 06/05/2009 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |