Permit: T09EL01393

Parcel: 136191510


Addresses:

8040 E NICARAGUA DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/13/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT AND MINERALLAC STRAP
2. SEPARATE EQUIPMENT GROUNDS AND TERMINATE PER INSTRUCTIONS ON PANEL DOOR
3. NEED CLEARANCE TO SPA PER NEC 680.40 AND 680.8 CHECK WITH TEP FOR CLEARANCE REQUIREMENTS -- THEY MAY REQUIRE 25' CLEARANCE
06/05/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled