Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTE: 408.4 DOES NOT ALLOW ABBREVIATIONS |
|
| 07/14/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CORRECTLY IDENTIFY CIRCUITS PER 408.4 2) WHERE ARE GROUND RODS ? 3) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT 4) PLEASE VERIFY PERMIT FOR NEW A/C UNIT 5) SERVICE ENERGIZED WITHOUT CLEARANCE |