Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 09/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SUB PANEL: 1) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 2) CLEAN SURFACE UNDER STRIP 250.12 3) REMOVE BOND JUMPER 4) PANEL NOT FLUSH IN COMBUSTIBLES |
|
| 09/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ISOLATE GROUNDS AND NEUTRALS IN SUB PANEL 2) SCREWS ON CONNECTORS LOOSE |
|
| 09/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NO LOADS CONNECTED AT THIS TIME 2) CALL FOR FINAL AFTER TEP TIE IN |