Permit: T09EL01315

Parcel: 12007751A


Addresses:

4219 S 12TH AV #01

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/23/2009 ELECTRIC - FINAL Approved WATER BOND OK. ELECTRIC PERMIT FROM 2008 FINALED OK
06/18/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NO WORK PROGRESS
06/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO GENERAL LABELING OF CIRCUITS - 408.4
2. FILL UNUSED PORTION OF OPENING WITH A NON-COMBUSTIBLE PRODUCT
3. NM CABLE TO EXTEND MIN. 1/4" INTO PANEL
4. FULLY IDENTIFY UNGROUNDED CONDUCTORS
5. #8 NM CABLE TO BE PROTECTED BY CIRCUIT BREAKER
PER 334.80
6. PLEASE VERIFY WATER BOND
7. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR
8. USE APPROVED HARDWARE TO ANCHOR RISER 1/4" MIN.