Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/23/2009 | ELECTRIC - FINAL | Approved | WATER BOND OK. ELECTRIC PERMIT FROM 2008 FINALED OK | |
| 06/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NO WORK PROGRESS |
|
| 06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO GENERAL LABELING OF CIRCUITS - 408.4 2. FILL UNUSED PORTION OF OPENING WITH A NON-COMBUSTIBLE PRODUCT 3. NM CABLE TO EXTEND MIN. 1/4" INTO PANEL 4. FULLY IDENTIFY UNGROUNDED CONDUCTORS 5. #8 NM CABLE TO BE PROTECTED BY CIRCUIT BREAKER PER 334.80 6. PLEASE VERIFY WATER BOND 7. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR 8. USE APPROVED HARDWARE TO ANCHOR RISER 1/4" MIN. |