Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2009 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 09/30/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* SUB PANEL: 1) CANNOT USE SHEET METAL THREAD SCREW FOR GROUND LUG 250.8 MAIN PANEL: 1) TIGHTEN LOOSE FITTINGS AT PANEL 2) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 3) WHAT ARE UNTERMINATED CONDUCTORS FOR ? |
|
| 09/21/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 09/18/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE GROUND RODS 2) BONDING OF WATER PIPE TO BE PER NEC 250.104 3) WILL NEED TO SEE ALL NEW WIRING |