Permit: T09EL01281

Parcel: 133260960


Addresses:

8135 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/22/2009 ELECTRIC - SERVICE UPGRADE Approved
09/30/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
SUB PANEL:
1) CANNOT USE SHEET METAL THREAD SCREW FOR GROUND LUG 250.8
MAIN PANEL:
1) TIGHTEN LOOSE FITTINGS AT PANEL
2) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8
3) WHAT ARE UNTERMINATED CONDUCTORS FOR ?
09/21/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
09/18/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE GROUND RODS
2) BONDING OF WATER PIPE TO BE PER NEC 250.104
3) WILL NEED TO SEE ALL NEW WIRING