Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) PANEL SERVICE AND SERVICE WIRE OK |
|
| 05/27/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK "SERVICE DISCONNECT" 2. SEAL OPENING IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL 3. TERMINATE NEUTRALS ON NEUTRAL BAR 4. TERMINATE GROUNDING ELECTRODE CONDUCTOR ON NEUTRAL BAR 5. BOND NIPPLE BETWEEN METER AND PANEL 6. TIGHTEN ALL LOCK NUTS 7. PVC RUN EXPOSED TO BE SCHEDULE 80 |