Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | ELECTRIC - RECONNECT | Approved | ||
| 07/07/2009 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) ADD 2 GROUND RODS MINIMUM 6' APART FOR PROOF OF ELECTRODE GROUND SYSTEM 2) ROMEX FROM CEILING OUTLET IN ROOM EAST OF KITCHEN TO BE REMOVED |
|
| 05/27/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST HOUSE NUMBERS VISIBLE FROM STREET 2) HAZARDOUS ELECTRICAL GARAGE JUNCTION BOX NOT TO CODE AT DISCONNECT 3) CLEAN UP ALL DISCONNECTS AT METER NOT TO CODE. EXPOSED ROMEX OPEN KNOCKOUTS. MISSING FUSES ETC... 4) LABEL CIRCUITS MAIN DEAD FRONT 5) NUMEROUS ADDITIONS TO REAR. PROVIDE PROOF OF PERMIT 6) 2 WIRE AND 2 WIRE WITH GROUND OUTLETS MIXED THRU-OUT 7) SMOKE ALARM BEDROOMS AND HALLWAYS 8) REPLACE BATH LIGHT FIXTURES WITH OUTLETS 9) EXPOSED WIRING BEDROOM CLOSET EXTENSION CORD NOT TO CODE 10) CODE COMPLIANT PERMIT MAY BE REQUIRED FOR ADDITIONS. CONSULT WITH ELECTRICIAN TO BRING ALL UP TO CODE |