Permit: T09EL01255

Parcel: 134231680


Addresses:

6652 E SCARLETT ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/03/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/21/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BELL BOX TO BE PROPERLY SECURED
2) BURY JUMPER BETWEEN GROUND RODS
3) CANNOT USE WHITE WIRE AS PHASE CONDUCTOR WHEN INSTALLED IN RACEWAY
4) INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANEL
5) NEED TO PULL PERMITS FOR ALL NEW WORK INCLUDING NEW A/C UNIT ON ROOF
6) OPEN 12" X 12" JUNCTION BOX FOR INSPECTION OR PROVIDE 6' LADDER
7) COMPLETE PREVIOUS INSPECTION ITEMS FROM 6/2/09
06/02/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*