Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/21/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BELL BOX TO BE PROPERLY SECURED 2) BURY JUMPER BETWEEN GROUND RODS 3) CANNOT USE WHITE WIRE AS PHASE CONDUCTOR WHEN INSTALLED IN RACEWAY 4) INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANEL 5) NEED TO PULL PERMITS FOR ALL NEW WORK INCLUDING NEW A/C UNIT ON ROOF 6) OPEN 12" X 12" JUNCTION BOX FOR INSPECTION OR PROVIDE 6' LADDER 7) COMPLETE PREVIOUS INSPECTION ITEMS FROM 6/2/09 |
|
| 06/02/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* |