Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOUTH COUNTER OUTLETS AND WEST END OUTLETS ON NORTH COUNTER ARE MIS-WIRED 2) IF IT FAILS AGAIN-ANOTHER REFEE WILL BE CHARGED |
|
| 06/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTLETS ARE STILL MIS-WIRED AND ABSENT OUTLET ABOVE DISHWASHER MUST BE IN PLACE 2) NO MORE INSPECTIONS WILL BE PERFORMED UNTIL REFEE HAS BEEN PAID TO DEVELOPMENT SERVICES |
|
| 06/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE LICENSED ELECTRICIAN CORRECT ALL KITCHEN COUNTER INOPERABLE GFI'S |
|
| 06/10/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL FOR FINAL INSPECTION AFTER POWER IS RESTORED |
|
| 06/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MAIN GROUNDING SYSTEM FOR MAIN PANEL 2) FILL OPEN KNOCKOUTS IN PANEL DEAD FRONT COVER 3) MAIN PANEL SHOWS A SUB-PANEL IN HOUSE. SUB-PANEL WAS FOUND, BUT COVER HAS BEEN PAINTED SHUT. OPEN SUB-PANEL FOR INSPECTION |