Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/20/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 30 AMP 220 BREAKER DBL LUGGED WITH #10 AND #12 2) SLEEVE ROMEX BACK PORCH TO 8' AFF OR REMOVE 3) #8 WIRE ON A/C COMPRESSOR-MAX 50 AMP FUSES 4) CONFIRM OUTLETS ON WEST COUNTER GFI PROTECTED 5) SMOKE DETECTORS REQUIRED IN ALL BEDROOMS AT LEAST 3' FROM REGISTERS AND BETWEEN 6" AND 12" OF CEILING IF WALL MOUNTED |