Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09EL01209

Parcel: 135023610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/02/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE HORNET NEST IN ELECTRIC PANEL
2) PROVIDE PROOF OF PERMITS FOR ALL NORTH AND EAST ADDITIONS
3) KITCHEN COUNTER AND BATHROOM OUTLETS MUST BE GFI PROTECTED
4) NEED SMOKE DETECTORS IN ALL BEDROOMS AND HALLWAY
5) ANY 3 PRONG OUTLETS ON THE OLD 2 WIRE SYSTEM MUST BE CHANGED BACK TO 2 PRONG OUTLETS OR MADE TO BE GFI
6) NEED OUTSIDE COMBUSTION AIR IN FURNACE ROOM