Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE HORNET NEST IN ELECTRIC PANEL 2) PROVIDE PROOF OF PERMITS FOR ALL NORTH AND EAST ADDITIONS 3) KITCHEN COUNTER AND BATHROOM OUTLETS MUST BE GFI PROTECTED 4) NEED SMOKE DETECTORS IN ALL BEDROOMS AND HALLWAY 5) ANY 3 PRONG OUTLETS ON THE OLD 2 WIRE SYSTEM MUST BE CHANGED BACK TO 2 PRONG OUTLETS OR MADE TO BE GFI 6) NEED OUTSIDE COMBUSTION AIR IN FURNACE ROOM |