Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE INFO FOR RISER/WEATHER HEAD 2) FINAL APPROVAL SUBJECT TO ACCEPTANCE OF WEATHERHEAD |
|
| 06/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. I.D. NEUTRALS AND GROUNDS 2. TOO MANY SPLICES IN PANEL 3. 1 #4 BARE PER ACORN CLAMP 4. PANEL DOOR MUST OPEN 90 DEG. 5. I.D. CIRCUIT BREAKERS 6. USE WATER PIPE CLAMP AT WATER HTR. |
|
| 06/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL NEW GROUNDING ELECTRODE SYSTEM BOND WATER AND GAS PIPING PER 250 NEC. 2) SUPPORT CONDUITS PER CODE 3) 2/0 COPPER OR 4/0 ALUM RISER AND FEED DOWN TO MAIN 200 AMP BREAKER 4) GROUND CONDUCTORS (EQUIP.) NEED TO BE GREEN INSULATION OR BARE. NEUTRAL CONDUCTORS WHITE INSULATION 5) INSTALL GROUND BAR FOR EQUIPMENT GROUND, TWISTED COPPER AND ALUMINUM WIRES NOT ALLOWED 6) INSTALL BOND BUSHING WHERE USING REDUCING WASHERS FOR CONDUIT TERM. 7) NO DBL LUGGING ON BREAKERS OR ON LUGS 8) USE QUALIFIED ELECTRICIAN |