Permit: T09EL01208

Parcel: 107081170


Addresses:

740 W TIPTON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE INFO FOR RISER/WEATHER HEAD
2) FINAL APPROVAL SUBJECT TO ACCEPTANCE OF WEATHERHEAD
06/23/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. I.D. NEUTRALS AND GROUNDS
2. TOO MANY SPLICES IN PANEL
3. 1 #4 BARE PER ACORN CLAMP
4. PANEL DOOR MUST OPEN 90 DEG.
5. I.D. CIRCUIT BREAKERS
6. USE WATER PIPE CLAMP AT WATER HTR.
06/18/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL NEW GROUNDING ELECTRODE SYSTEM BOND WATER AND GAS PIPING PER 250 NEC.
2) SUPPORT CONDUITS PER CODE
3) 2/0 COPPER OR 4/0 ALUM RISER AND FEED DOWN TO MAIN 200 AMP BREAKER
4) GROUND CONDUCTORS (EQUIP.) NEED TO BE GREEN INSULATION OR BARE. NEUTRAL CONDUCTORS WHITE INSULATION
5) INSTALL GROUND BAR FOR EQUIPMENT GROUND, TWISTED COPPER AND ALUMINUM WIRES NOT ALLOWED
6) INSTALL BOND BUSHING WHERE USING REDUCING WASHERS FOR CONDUIT TERM.
7) NO DBL LUGGING ON BREAKERS OR ON LUGS
8) USE QUALIFIED ELECTRICIAN