Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ITEMS ON LIST ALL DONE CHANGED PANELS OK |
|
| 06/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO REMOVE WIRES FROM BEHIND PANEL ALL DEDICATED SPACE |
|
| 06/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE BOND BUSHINGS, CLOSE NIPPLES WHEN USING RE-WASHERS AT TERMINATIONS 2. NO CONDUIT, LOAD TERMINATIONS AT TOP/BACK OF PANEL SEE LISTING NOTES ON DOOR BY MANUF. THIS AREA IS DEDICATED FOR LINE BUSS 3. BARRIER MISSING IN FRONT OF BUSS AT TOP OF PANEL |
|
| 06/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |