Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/01/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER ACORN CLAMP 2) RECEPTACLE COVER TO BE PER 406.8 3) MAST SUPPORT ATTACHMENT TO BE WITHIN 3' OF END OF RISER 4) RECALL AFTER CROSS OVER |
|
| 09/01/2009 | ELECTRIC - SERVICE UPGRADE | Denied | 1) 2 GROUND RODS AND WATER BOND 2) GAS LINE (METAL) ALSO REQUIRES A BOND TO SERVICE 2005 NEC 250 3) THE ELECTRIC CODE (2005 SECTION 230) CLEARANCE OVER ROOF REQUIRES 8', THE OVER HEAD LINES ARE TO BE 8' AF ROOF SO SOMEONE CAN WALK SAFELY UNDER THEM. SEE ABOVE ROOF CLEARANCE REQUIRED IN ELECTRIC CODE |
|
| 08/28/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) NO ANSWER AT DOOR-NO ACCESS 2) LOCK UP DOGS |