Permit: T09EL01106

Parcel: 124120910


Addresses:

1340 E 12TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/05/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT TERMINATE EMT INTO PLASTIC @ PANEL NEEDS TO BE METALLIC OR INSTALL BONDING BUSHING
2. IS 6" X 6" JUNCTION BOX GROUNDED
3. LABEL CIRCUITS IN PANEL (PANEL DIRECTORY)
05/29/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) RECALL WHEN WORK COMPLETE
2) INSTALL FEEDER
3) STRAP GEC
4) OK GROUND RODS, WATER AND GAS BOND