Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT TERMINATE EMT INTO PLASTIC @ PANEL NEEDS TO BE METALLIC OR INSTALL BONDING BUSHING 2. IS 6" X 6" JUNCTION BOX GROUNDED 3. LABEL CIRCUITS IN PANEL (PANEL DIRECTORY) |
|
| 05/29/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL WHEN WORK COMPLETE 2) INSTALL FEEDER 3) STRAP GEC 4) OK GROUND RODS, WATER AND GAS BOND |