Permit: T09EL01068

Parcel: 125090220


Addresses:

2549 E BROADWAY BL


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01068

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
06/22/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
06/22/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE CONDUCTORS NOT SIZED PROPERLY 4 - 200 AMP COMMERCIAL SERVICE. RACEWAY NOT SIZED PROPERLY.
2. ENTIRE SERVICE DROP TO BE UPGRADED TO 200 AMP COMMERCIAL SERVICE
3. INSTALL RACEWAY FROM SERVICE DISCONNECT TO PANEL
4. GROUNDS & NEUTRALS TO BE SEPARATE @ SUB-PANEL
5. BOND SERVICE RACEWAYS PER NEC 250.92
6. SEAL OPEN KNOCKOUTS IN PANEL
7. NEED PANEL DIRECTORY
8. INSTALL PROPER FITTINGS ON RACEWAYS
9. INSTALL RACEWAYS AS COMPLETE SYSTEM TO ALL BOXES
NO OPEN CONDUCTORS
10. NEED PROPER WORKING CLEARANCES IN FRONT OF PANEL NEC 110.26
11. LB COVER TO BE ACCESSIBLE
12. MOUNT TIME CLOCK PROPERLY
13. INSTALL BLANKS OPEN BREAKER POSITIONS PANEL
CANNOT USE ELECTRICAL TAPE
14. RECALL WHEN READY
05/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED STRAPPING ABOVE & BELOW METER
NEED TO SEE WIRES IN PANEL