Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01068
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
06/22/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS NOT SIZED PROPERLY 4 - 200 AMP COMMERCIAL SERVICE. RACEWAY NOT SIZED PROPERLY. 2. ENTIRE SERVICE DROP TO BE UPGRADED TO 200 AMP COMMERCIAL SERVICE 3. INSTALL RACEWAY FROM SERVICE DISCONNECT TO PANEL 4. GROUNDS & NEUTRALS TO BE SEPARATE @ SUB-PANEL 5. BOND SERVICE RACEWAYS PER NEC 250.92 6. SEAL OPEN KNOCKOUTS IN PANEL 7. NEED PANEL DIRECTORY 8. INSTALL PROPER FITTINGS ON RACEWAYS 9. INSTALL RACEWAYS AS COMPLETE SYSTEM TO ALL BOXES NO OPEN CONDUCTORS 10. NEED PROPER WORKING CLEARANCES IN FRONT OF PANEL NEC 110.26 11. LB COVER TO BE ACCESSIBLE 12. MOUNT TIME CLOCK PROPERLY 13. INSTALL BLANKS OPEN BREAKER POSITIONS PANEL CANNOT USE ELECTRICAL TAPE 14. RECALL WHEN READY |
|
05/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED STRAPPING ABOVE & BELOW METER NEED TO SEE WIRES IN PANEL |