Permit: T09EL01055

Parcel: 130171860


Addresses:

4129 E 29TH ST #101

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/27/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. COMPLETE ITEM #5 FROM PREVIOUS INSPECTION
THIS ITEM IS ABOVE CEILING ON 3/4" EMT USED TO FEED NEW RECEPTACLES
2. OK NEW WALLS
05/08/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE CONNECTORS LISTED FOR USE WITH MC CABLE
2. MC CABLE TO BE STRAPPED/STAPLED WITHIN 12" OF CONNECTIONS
3. REMOVE RECEPTACLES FOR INSPECTION
4. CANNOT SECURE BOX BY RUNNING SCREWS THROUGH BOX (SINGLE GANG BOX)
5. NEED COUPLING WHERE EMT COMES TOGETHER
6. RECALL WHEN READY