Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEM #5 FROM PREVIOUS INSPECTION THIS ITEM IS ABOVE CEILING ON 3/4" EMT USED TO FEED NEW RECEPTACLES 2. OK NEW WALLS |
|
| 05/08/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE CONNECTORS LISTED FOR USE WITH MC CABLE 2. MC CABLE TO BE STRAPPED/STAPLED WITHIN 12" OF CONNECTIONS 3. REMOVE RECEPTACLES FOR INSPECTION 4. CANNOT SECURE BOX BY RUNNING SCREWS THROUGH BOX (SINGLE GANG BOX) 5. NEED COUPLING WHERE EMT COMES TOGETHER 6. RECALL WHEN READY |