Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH #2 & 4 OF PREVIOUS INSPECTION |
|
| 06/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SERVICE: 1. SECURE RISER (#3 PREVIOUS INSPECTION) 2. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH -- 250.119 3. CANNOT TRIM CONDUCTOR STRANDS TO FIT INTO LUGS 4. TIGHTEN LOOSE CONDUCTOR TERMINATIONS 5. ONLY ONE CONDUCTOR PER GROUND ROD CLAMP AND INSTALLED PER MANUFACTURES REQUIREMENTS PANEL: 1. FILL UNUSED OPENING IN COVER 2. SEPARATE GROUNDING AND GROUNDED CONDUCTORS AT SUB-PANEL 250.24 |
|
| 05/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS 2) LARGER THAN #8 IN RACEWAY TO BE STRANDED 3) SECURE RISER FOR NO MOVEMENT 4) MANUFACTURERS HOLDOWN NEEDED FOR BACK FED BREAKE 408.16 5) USE APPROVED CLAMP FOR GROUNDING ELECTRODE CONDUCTOR |
|
| 05/27/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTORS TO BE IN CONTINUOUS RACEWAY 2. AN EQUIPMENT GROUND CONDUCTOR IS NEEDED 3. A 2ND GROUND ROD IS NEEDED AND SECURE CONDUCTOR TO STRUCTURE AND TO PANEL 4. LABEL BREAKERS 5. SUPPORT CONDUIT ON SIDE OF PANEL 6. SUB-DISCONNECT NOT MADE UP TO CODES *PLEASE HAVE QUALIFIED ELECTRICIAN DO WORK |