Permit: T09EL01049

Parcel: 138181230


Addresses:

209 E SUSANA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
06/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH #2 & 4 OF PREVIOUS INSPECTION
06/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SERVICE:
1. SECURE RISER (#3 PREVIOUS INSPECTION)
2. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH -- 250.119
3. CANNOT TRIM CONDUCTOR STRANDS TO FIT INTO LUGS
4. TIGHTEN LOOSE CONDUCTOR TERMINATIONS
5. ONLY ONE CONDUCTOR PER GROUND ROD CLAMP AND INSTALLED PER MANUFACTURES REQUIREMENTS

PANEL:
1. FILL UNUSED OPENING IN COVER
2. SEPARATE GROUNDING AND GROUNDED CONDUCTORS AT SUB-PANEL 250.24
05/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS
2) LARGER THAN #8 IN RACEWAY TO BE STRANDED
3) SECURE RISER FOR NO MOVEMENT
4) MANUFACTURERS HOLDOWN NEEDED FOR BACK FED BREAKE 408.16
5) USE APPROVED CLAMP FOR GROUNDING ELECTRODE CONDUCTOR
05/27/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTORS TO BE IN CONTINUOUS RACEWAY
2. AN EQUIPMENT GROUND CONDUCTOR IS NEEDED
3. A 2ND GROUND ROD IS NEEDED AND SECURE CONDUCTOR TO STRUCTURE AND TO PANEL
4. LABEL BREAKERS
5. SUPPORT CONDUIT ON SIDE OF PANEL
6. SUB-DISCONNECT NOT MADE UP TO CODES

*PLEASE HAVE QUALIFIED ELECTRICIAN DO WORK