Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/12/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HUB AT RISER TO GUTTER NOT APPROVED FOR BONDING AT SERVICES, 110.3 & 250.92 2) NO BUSHING ON 2ND NIPPLE TO SERVICE #2 300.4 F |