Permit: T09EL01046

Parcel: 113100550


Addresses:

1716 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/13/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/12/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HUB AT RISER TO GUTTER NOT APPROVED FOR BONDING AT SERVICES, 110.3 & 250.92
2) NO BUSHING ON 2ND NIPPLE TO SERVICE #2 300.4 F