Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED OUTSIDE LIGHT AT DOOR 2. 250V OUTLET - BOX FULL OF PLASTER - UNCOVER & PLATE 3. RECEPTACLES FULL OF PAINT - REPLACE 4. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL 5. RECONNECT GROUND CLAMP AT ROD 6. ONLY ONE CONDUCTOR PER TERMINAL LUG AT MAIN DISCONNECT 7. RE-TIGHTEN CONDUCTOR TERMINATIONS AT MAIN DISCONNECT 8. CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF DISCONNECT AND PANEL 9. RE-SUPPORT GROUNDING CONDUCTORS TO STRUCTURE 10. BREAKER WILL NEED TO BE LABELED 11. COOLER AND WIRING NOT UP TO CODE |