Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T09EL01005
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/13/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
05/04/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1) H20 BOND REQUIRED 2) LABEL ALL CIRCUITS 3) CHECK SIZE OF WIRE METER TO TIE IN. LOOKS LIKE #6 CU.=60 AMPS MAX |