Permit: T09EL00951

Parcel: 10709066D

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL00951

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
05/13/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DOOR HARDWARE ON BOTH DOORS DOESN'T MEET EGRESS
2) NEED LANDING ON STEPS AT FRONT DOOR
3) NEED GFCI RECEPTACLES AT KITCHEN (NEW WIRING IN BEDROOM AND H20 HTR)
4) NEED COOKING APPLIANCES AT THIS TIME
5) I CONSIDER THIS MOBILE HOME TO BE UNSAFE STRUCTUALLY
04/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ROMEX FOR H20 HTR NEEDS BUSHING AND ROMEX CONNECTOR SHOULD BE IN CONDUIT-STOPPED INSPECTION