Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BASEBOARD NOT TO BE INSTALLED ON COMBUSTIBLE SURFACE, SEE INSTALLATION INSTRUCTIONS. 2. OK UNDER UNIT |
|
| 04/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE OWNERS INSTALLATION INSTRUCTIONS FOR BASEBOARD HEATERS - SEE MOUNTING INSTRUCTIONS FOR FIRE HAZARD. 2. TYPE NM ROMEX TO BE SUPPORTED PER 334 NEC 334.15 AND 334.30 AND 300.4 B 3. HOW IS THE CABLE TERMINATED AT BASE BOARD? |
|
| 04/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECALL INSP. HAVE CONTR. ON SITE |