Permit: T09EL00841

Parcel: 111051570

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/03/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/27/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT TERMINATE 2 NEUTRALS UNDER SAME LUG IN PANEL BOARD
2) INSTALL PROPER SIZE FUSES IN FUSE BOX FOR BRANCH CIRCUITS
3) RECALL WHEN READY
06/08/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CONNECT GROUNDING ELECTRODE CONDUCTOR TO UNIT #2 TO GROUND ROD OR GROUNDING ELECTRODE CONDUCTOR. NOT TO PANEL GROUND BAR OF UNIT #1
2) RECALL AFTER SWING OVER COMPLETE
3) OK GROUND RODS, GAS AND WATER BOND