Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/27/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT TERMINATE 2 NEUTRALS UNDER SAME LUG IN PANEL BOARD 2) INSTALL PROPER SIZE FUSES IN FUSE BOX FOR BRANCH CIRCUITS 3) RECALL WHEN READY |
|
| 06/08/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CONNECT GROUNDING ELECTRODE CONDUCTOR TO UNIT #2 TO GROUND ROD OR GROUNDING ELECTRODE CONDUCTOR. NOT TO PANEL GROUND BAR OF UNIT #1 2) RECALL AFTER SWING OVER COMPLETE 3) OK GROUND RODS, GAS AND WATER BOND |