Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00840
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WHERE IS FIXTURE GROUNDING PER 410.20 AND 410.21 2. WHERE IS CONDUCTOR OVER-CURRENT PROTECTION 240.4 3. NM CABLE NOT ALLOWED FOR WET LOCATION 4. DO BURIAL DEPTHS MEET REQUIREMENTS OF 300.5 5. ARE CONDUCTORS AT POLE HEAD RATED FOR WET LOCATION AND SUNLIGHT RESISTANT |