Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00821
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES FOR 3558 E. WILLARD |
|
| 07/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL 2) INSTALL PROPER SIZE EQUIPMENT GROUNDS AND BONDING JUMPERS TO METAL BOXES. NEC 250.122 3) PLEASE EXPLAIN 2 PLE 60A FOR RANGE. SEE NEC 210.21 4) PLEASE PROVIDE COPY OF PERMITS FOR ALL NEW WORK, WATER HEATER, A/C UNIT, ETC.... |