Permit: T09EL00813

Parcel: 107131580


Addresses:

2635 N STONE AV #06

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/29/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) CONTRACTOR ABANDONED MOST WIRING NOT USED
04/23/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/23/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTR. TO BRING ELECTRICAL INSTALLATION UP TO CODE, EXISTING WORK DONE WITHOUT PERMITS. MET WITH ELECTRICIAN
04/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE CONTR. TO CONTACT INSP. DAN @ 909-5173
MEET ON SITE FOR INSPECTION
THE WORK DONE IS NOT UP TO CODE
STILL SOME EXISTING CODE VIOLATIONS
A REINSPECTION FEE WILL BE ASSESSED NEXT INSP. IF WORK NOT UP TO CODE (2005 NEC)

PROVIDE LADDER FOR ROOF INSPECTION
UNLOCK BACK DOORS BEHIND NEW PANEL
04/16/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE
2. INSTALL BOND BUSHINGS ON NIPPLE ON SUPPLY SIDE OF SERVICE 250.92 NEC
3. BOND WATER AND GAS PIPING
4. INSTALL UNIT # ON BLDG.
5. THIS UNIT HAS MULTIPLE ELECTRICAL CODE VIOLATIONS, OUTSIDE WIRING NOT TO CODE, NON-WEATHERPROOF DEVICES, OPEN SPLICES, HAVE CONTR. CHECK ROOF WIRING
OVERFUSING IN SUB-PANEL LOOSE, UNSUPPORTED CONDUITS, LIGHT FIXTURES IN NEED OF REPAIR.

OBTAIN THE SERVICES OF A LICENSED OR QUALIFIED ELECTRICIAN TO REPAIR ITEMS. RECALL INSP. WHEN DONE