Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09EL00794

Parcel: 131043540


Addresses:

4933 E 28TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT RUN OPEN CONDUCTORS. INSTALL IN APPROVED RACEWAY OR CABLE ASSEMBLY
2) STRAP GROUNDS TO BLDG
3) LABEL BREAKERS
4) SEAL OPEN BREAKER POSITION
5) REGROUND PHONE AND CABLE SYSTEMS
6) OK GROUND RODS
7) OK GAS AND WATER BOND