Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/24/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) BOND GAS PIPING ON HOUSE SIDE OF GAS METER
2) LABEL BREAKERS IN PANEL
3) RECALL AFTER CORRECTIONS MADE
06/19/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL 2 GROUND RODS MINIMUM 6' APART
2) INSTALL GROUND CLAMPS LISTED FOR DIRECT BURY AND FOR USE ON GROUND RODS
3) COMPLETELY DRIVE GROUND RODS BELOW GRADE
4) BOND GAS AND WATER PIPING
5) INSTALL ROOF JACK
6) EXCEEDED BENDING RADIUS OF CONDUCTORS
7) CANNOT VERIFY SIZE OF CONDUCTOR OR IF SUN LIGHT RESISTANT. DO NOT SEE ANY MARKINGS
8) NEED PANEL DIRECTORY
9) SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL