Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BOND GAS PIPING ON HOUSE SIDE OF GAS METER 2) LABEL BREAKERS IN PANEL 3) RECALL AFTER CORRECTIONS MADE |
|
| 06/19/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL 2 GROUND RODS MINIMUM 6' APART 2) INSTALL GROUND CLAMPS LISTED FOR DIRECT BURY AND FOR USE ON GROUND RODS 3) COMPLETELY DRIVE GROUND RODS BELOW GRADE 4) BOND GAS AND WATER PIPING 5) INSTALL ROOF JACK 6) EXCEEDED BENDING RADIUS OF CONDUCTORS 7) CANNOT VERIFY SIZE OF CONDUCTOR OR IF SUN LIGHT RESISTANT. DO NOT SEE ANY MARKINGS 8) NEED PANEL DIRECTORY 9) SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL |