Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00754
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE LOCK FROM SERVICE PANEL 2. PROVIDE LADDER FOR ROOF INSPECTION 3. 120V CONV. OUTLETS IN FOOD PREP AREAS TO BE GFI PROTECTED 4. COVER MISSING TO RECEPT. INSIDE WEST WALL |