Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T09EL00739
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/29/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) MEET WITH GUS TO DISCUSS PROJECT-HE IS TAKING OVER |
|
| 10/25/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) CALLED TWICE-MESSAGE STATES-NO REMAINING TIME-LOCKED AND NO ACCESS 2) UNFINISHED UNITS WILL RESULT IN A REFEE 3) COMPLETE ALL ITEMS AND UNITS |
|
| 10/21/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER BILL |
|
| 10/04/2010 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) FINISH ALL UNITS COMPLETE BEFORE NEXT INSPECTION |
|
| 09/21/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 09/20/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED FITITNGS FOR CONDUIT LB 2) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS WITH APPROVED FITTING 3) STRAP CONDUIT ONSIDE OF PANEL 4) STRAP AND SUPPORT CONDUIT OFF OF ROOF 5) TIGHTEN LOOSE FITTINGS 6) LAB TO BE ACCESSIBLE COVER 7) SEPERATE NEUTRALS AND GROUNDS AT A/C DISCONNECT 8) HOME RUN TO REAR UNIT-STRAP AND SUPPORT CONDUIT, NO MORE THAN 360 DEGREE IN CONDUIT RUN 9) REFEE NEEDS TO BE PAID BEFORE NEXT INSPECTION |
|
| 09/15/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED, NO ACCESS AND NO MESSAGE 2) PLUMBING PERMIT IS STILL IN APPLIED STATUS 3) A REFEE MAY BE ASSESED FOR UNECESSARY INSPECTIONS |
|
| 09/07/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 09/01/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 08/30/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3808 REMOVE BONDING SCREW AT SUB PANEL 2) FILL UNUSED OPENINGS AT SUB PANEL 3) CONDUCTOR TO HEAT PUMP/AC REMOVED 4) FINISH #7 AND 12 WATER BOND NOW APPEARS CUT SINCE PREVIOUS INSPECTION |
|
| 08/20/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) WORK NOT PROGRESSSING |
|
| 08/16/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 03/04/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) LOCK BOX WOULD NOT OPEN WITH CODES 2) NO EVIDENCE OF WORK PROGRESS 3) PLEASE PAY REINSPECTION FEE 4) NO FURTHER INSPECTIONS UNTIL VERIFICATION OF QUALIFIED ELECTRICIAN-WORK IS NOT TO MINIMUM STANDARD OF NEC |
|
| 01/05/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) UNCOVER UNDERGROUND TO INSPECT FOR 300.5 2) BREAKER LABELING TO BE PER 408.4 3) UNITS LOCKED-ONLY 3808 OPEN 4) FINISH ITEMS 5,6,7,8,9,10,11,12 & 13 5) PLEASE VERIFY QUALIFIED ELECTRICIAN 6) A REFEE MAY BE ASSESSED |
|
| 12/22/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) UNIT NUMBERS NOT POSTED 2) MISSING MAIN BREAKER COVERS 3) MISSING MAIN BREAK 3812 4) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE REMOVE VEGITATION 5) LABEL PANELS AND BREAKERS 6) KITCHEN RECEPTS TO BE GFI PROTECTED 7) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 NEW DEVICES AND PLATES 8) GROUNED RECEPTS ON UNGROUNDED CIRCUITS 9) PLEASE VERIFY PERMITS FOR NEW WIRING 10) CONNECTOR NEEDED AT NEW HOOD 11) WIRING TO BACK 2ND BLDG NOT TO CODE 12) MISSING GAS BOND CONDUCTOR 13) PLEASE VERIFY PLUMBING PERMITS |