Permit: T09EL00739

Parcel: 120073480


Addresses:

3808 S LIBERTY AV


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09EL00739

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2010 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/29/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) MEET WITH GUS TO DISCUSS PROJECT-HE IS TAKING OVER
10/25/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
1) CALLED TWICE-MESSAGE STATES-NO REMAINING TIME-LOCKED AND NO ACCESS
2) UNFINISHED UNITS WILL RESULT IN A REFEE
3) COMPLETE ALL ITEMS AND UNITS
10/21/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER BILL
10/04/2010 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) FINISH ALL UNITS COMPLETE BEFORE NEXT INSPECTION
09/21/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
09/20/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED FITITNGS FOR CONDUIT LB
2) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS WITH APPROVED FITTING
3) STRAP CONDUIT ONSIDE OF PANEL
4) STRAP AND SUPPORT CONDUIT OFF OF ROOF
5) TIGHTEN LOOSE FITTINGS
6) LAB TO BE ACCESSIBLE COVER
7) SEPERATE NEUTRALS AND GROUNDS AT A/C DISCONNECT
8) HOME RUN TO REAR UNIT-STRAP AND SUPPORT CONDUIT, NO MORE THAN 360 DEGREE IN CONDUIT RUN
9) REFEE NEEDS TO BE PAID BEFORE NEXT INSPECTION
09/15/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
1) LOCKED, NO ACCESS AND NO MESSAGE
2) PLUMBING PERMIT IS STILL IN APPLIED STATUS
3) A REFEE MAY BE ASSESED FOR UNECESSARY INSPECTIONS
09/07/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
09/01/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
08/30/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3808 REMOVE BONDING SCREW AT SUB PANEL
2) FILL UNUSED OPENINGS AT SUB PANEL
3) CONDUCTOR TO HEAT PUMP/AC REMOVED
4) FINISH #7 AND 12 WATER BOND NOW APPEARS CUT SINCE PREVIOUS INSPECTION
08/20/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) WORK NOT PROGRESSSING
08/16/2010 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
03/04/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) LOCK BOX WOULD NOT OPEN WITH CODES
2) NO EVIDENCE OF WORK PROGRESS
3) PLEASE PAY REINSPECTION FEE
4) NO FURTHER INSPECTIONS UNTIL VERIFICATION OF QUALIFIED ELECTRICIAN-WORK IS NOT TO MINIMUM STANDARD OF NEC
01/05/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) UNCOVER UNDERGROUND TO INSPECT FOR 300.5
2) BREAKER LABELING TO BE PER 408.4
3) UNITS LOCKED-ONLY 3808 OPEN
4) FINISH ITEMS 5,6,7,8,9,10,11,12 & 13
5) PLEASE VERIFY QUALIFIED ELECTRICIAN
6) A REFEE MAY BE ASSESSED
12/22/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) UNIT NUMBERS NOT POSTED
2) MISSING MAIN BREAKER COVERS
3) MISSING MAIN BREAK 3812
4) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE REMOVE VEGITATION
5) LABEL PANELS AND BREAKERS
6) KITCHEN RECEPTS TO BE GFI PROTECTED
7) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 NEW DEVICES AND PLATES
8) GROUNED RECEPTS ON UNGROUNDED CIRCUITS
9) PLEASE VERIFY PERMITS FOR NEW WIRING
10) CONNECTOR NEEDED AT NEW HOOD
11) WIRING TO BACK 2ND BLDG NOT TO CODE
12) MISSING GAS BOND CONDUCTOR
13) PLEASE VERIFY PLUMBING PERMITS