Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* UNIT 1: 1) BLANK SPACES IN SERVICE PANEL MISISNG 50/50 NOT CORRECT SIZE FOR CIRCUIT, EXTERIOR, TWO 30 AMP RECEPTS REMOVE CIRCUIT OR INSTALL CORRECT SIZE BREAKER ------------------------------------------------------------------------------------------------- UNIT 2: 1) LABEL ALL CIRCUITS AND RECALL FINAL |
|
| 04/10/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE RECALL FOR MONDAY, I WILL REINSPECT, BEFORE 10:00 AM AND SEND IN CLEARANCE 2) UNIT #2 OK |
|
| 04/09/2009 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 04/07/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* UNIT 1: 1) 2 POLE 50/50 AMP BREAKER, PROTECTING #10 CU WIRE 2) LABEL CIRCUITS 3) BLANK SPACERS IN MISSING K.O. SLOTS 4) (PUMP AND MOTOR TIED TOGETHER) OPEN SPLICED ON ROOF ------------------------------------------------------------------------------------------------- UNIT 2: 1) LABEL ALL CIRCUITS 2) TWO POLE 30/30 AMP BREAKER TOO BE OF SAME MANUFACTURER AS MAIN 3) 20 AMP BREAKER DBL FED NEED ONE BREAKER PER CIRCUIT 4) EACH CIRCUIT TO BE ON IT'S OWN BREAKER, TO MANY CIRCUITS NOT ENOUGH BREAKERS 5) ONE SPACE IN SUB-PANEL BREAKER MISSING ------------------------------------------------------------------------------------------------ BOTH UNITS NEED GROUNDED TYPE RECEPTACLES USED, NO GROUND RUN TO SUB-PANEL |