Permit: T09EL00736

Parcel: 120070290


Addresses:

135 W AJO WY #01

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
UNIT 1:
1) BLANK SPACES IN SERVICE PANEL MISISNG 50/50 NOT CORRECT SIZE FOR CIRCUIT, EXTERIOR, TWO 30 AMP RECEPTS REMOVE CIRCUIT OR INSTALL CORRECT SIZE BREAKER
-------------------------------------------------------------------------------------------------
UNIT 2:
1) LABEL ALL CIRCUITS AND RECALL FINAL
04/10/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE RECALL FOR MONDAY, I WILL REINSPECT, BEFORE 10:00 AM AND SEND IN CLEARANCE
2) UNIT #2 OK
04/09/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/07/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
UNIT 1:
1) 2 POLE 50/50 AMP BREAKER, PROTECTING #10 CU WIRE
2) LABEL CIRCUITS
3) BLANK SPACERS IN MISSING K.O. SLOTS
4) (PUMP AND MOTOR TIED TOGETHER) OPEN SPLICED ON ROOF
-------------------------------------------------------------------------------------------------
UNIT 2:
1) LABEL ALL CIRCUITS
2) TWO POLE 30/30 AMP BREAKER TOO BE OF SAME MANUFACTURER AS MAIN
3) 20 AMP BREAKER DBL FED NEED ONE BREAKER PER CIRCUIT
4) EACH CIRCUIT TO BE ON IT'S OWN BREAKER, TO MANY CIRCUITS NOT ENOUGH BREAKERS
5) ONE SPACE IN SUB-PANEL BREAKER MISSING
------------------------------------------------------------------------------------------------
BOTH UNITS NEED GROUNDED TYPE RECEPTACLES USED, NO GROUND RUN TO SUB-PANEL