Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED PER 250.64(E) 2. ONLY ONE CONDUCTOR PER ACORN CLAMP AND INSTALL AS PER MANUFACTURE 3. GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED TO GROUNDED CONDUCTOR 250.24 4. NO MAIN BREAKERS INSTALLED 5. NO SECONDARY FEEDERS INSTALLED |