Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2009 | ELECTRIC - RECONNECT | Denied | MET ON SITE WITH HENRY DURAZO SENIOR RESIDENTIAL INSPECTOR: 1) FOUND WORK TO INTERIOR CONTINUES TO INCLUDE BATHROOM REMODEL (NEW) 2) UNDER SIZED HEADER AT REAR PORCH 3) EXTERIOR SIDING NOT PROPERLY FASTENED TO CODE 4) EXTENSIVE ELECTRICAL WORK EXPOSED TO REAR ADDITION STORAGE ROOM 5) ROOM ADDITION BROKEN UP INTO 2 SEPERATE ROOMS WITH ELECTRICAL COVERED WITH SHEETROCK 6) WORK FROM PREVIOUS PERMIT WAS NEVER COMPLETED 7) NO RECORDS FOUND OF ANY INSPECTION APPROVALS 8) REASON FOR CONCERN, ELECTRICAL WORK IN REAR ADDITION THAT IS EXPOSED NOT TO CODE 9) SOME ELECTRICAL HAS BEEN COVERED WITH SHEETROCK 10) EXTENSION CORD RUNNING FROM NEXT DOOR 11) SEE PHOTOS TAKEN |
|
| 04/06/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTES 1, 2 AND 14 FROM PREVIOUS |
|
| 03/26/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST HOUSE NUMBERS 2) PROVIDE PROOF PERMIT REAR ADDITIONS 3) GFCI PROTECT OUTLETS AT PANEL 4) OMIT HAZARDOUS ZIP CORD WIRING EXT. LIGHT AT PANEL 5) SEAL KNOCKOUTS MAIN PANEL BOTTOM 6) MIXED BREAKERS IN PANEL 7) LABEL CIRCUITS 8) GFCI PROTECT ALL EXTERIOR OUTLETS 9) GFCI PROTECT KITCHEN COUNTER OUTLETS 10) FURR OUTS IN BEDROOMS ELECTRICAL MUST BE IN APPROVED BOXES 11) REMOVE BATH LIGHT FIXTURE OUTLET NOT GFCI PROTECTED 12) SMOKE ALARMS BEDROOMS AND HALLWAY 13) BEDROOM BARS MUST OPERATE WITHOUT USE OF SEPERATE TOOLS 14) REAR ADDITION TO INCLUDE PORCH AND 2 ROOMS WITH ELECTRICAL |