Permit: T09EL00659

Parcel: 11804193A

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/10/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
11/25/2009 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) BOND GAS LINE
2) LABEL CIRCUITS MAIN PANEL
3) RELOCATE SMOKE ALARMS MAY NOT BE WITHIN 36" FORCED AIR REGISTERS, RELOCATE 6"-12" FROM CEILING
04/01/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFCI RECEPTS REQUIRED KITCHEN
2) SMOKE DETECTORS EACH BEDROOM AND ENTRY TO BEDROOMS
3) EXPOSED ROMEX IN LAUNDRY ROOM
4) KITCHEN SHELF COVERING SUB PANEL COVER REMOVE FOR INSPECTION, IF SUB PANEL IS AN UNGROUNDED SYSTEM, ALL GROUND TYPE WALL RECEPTS TO BE SAME OR ON GFCI PROTECTION
5) VERIFY GROUND SYSTEM CU TO IRON PIPE CONNECTION AT FRONT WALL NO DIELECTRIC UNION
6) AL TO CU. GRD. A/C UNIT
03/27/2009 ELECTRIC - RECONNECT Denied NO KEY IN LOCK BOX
PLEASE RECALL