Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00651
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/14/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES AND PANEL 2. STRAP MC CABLE WITHIN 12" OF CONNECTIONS OR REMOVE CABLE 3. STRAP METAL FLEX WITHIN 12" OF CONNECTIONS 4. SECURE JUNCTION BOXES TO STRUCTURE 5. PROPERLY INSTALL T&P LINE TO WATER HEATER CANNOT USE PVC NEEDS TO BE COPPER OR CPVC. NEEDS TO BE SLOPED TO DRAIN. 6. CLEAN UP EXPOSED WIRING AND DAMAGED EMT OUTSIDE REAR OF UNIT 7. INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL ENSURE HAVE PROPER OVERCURRENT SETTING FOR CIRCUITS |
|
| 03/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. UNIT TO BE OPEN FOR INSPECTION 2. PLEASE PROVIDE ROOF ACCESS 3. PLEASE PROVIDE ACCESS TO ELECTRIC SERVICE |