Permit: T09EL00575

Parcel: 136150230

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/25/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPEN KNOCKOUTS IN PANEL
2. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES
3. HAVE WHITE WIRE USED AS PHASE CONDUCTOR WITH NO NEUTRAL FOR THIS CIRCUIT IN RACEWAY ON 120V CIRCUIT
4. EQUIPMENT GROUNDS FOR 30 AMP. CIRCUITS
TO BE #10 AWG MIN.