Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS IN PANEL 2. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES 3. HAVE WHITE WIRE USED AS PHASE CONDUCTOR WITH NO NEUTRAL FOR THIS CIRCUIT IN RACEWAY ON 120V CIRCUIT 4. EQUIPMENT GROUNDS FOR 30 AMP. CIRCUITS TO BE #10 AWG MIN. |