Permit: T09EL00560

Parcel: 106040930


Addresses:

3437 N FONTANA AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/02/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) CARPORT REMOVED
2) REMAINING PORCH ON SOUTH ATTACHED NOT PER CODE
3) REPAIR AND RECALL 2090
08/26/2009 ELECTRIC - RECONNECT Cancelled IVRS - RI canceled
08/25/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROOF OF PERMIT ATTACHED CARPORT. NOT STRUCTUALLY SOUND. 4 X 4 HEADERS OVERSPANNED. NO POST BASE CONNECTION. 2 X 6 RAFTERS OVERSPANNED. ELECTRICAL AT CARPORT NOT TO CODE
2) NOTE 5 & 8 FROM PREVIOUS
3) EXPOSE ROMEX ROOM OFF CARPORT
4) OMIT HAZARDOUS WIRING NOT TO CODE LIVING ROOM FAN
5) 2 WIRE OUTLETS AND 2 WIRE WITH GROUND MIXED THROUGHOUT
03/17/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CARPORT NOT STRUCTUALLY SOUND-WAS IT PERMITTED ?
2) ALL ELECTRICAL WORK IN SHED IS NOT PER CODE-WAS IT PERMITTED ?
3) WASHER STAND PIPE NOT TRAPPED
4) GUTTER DRAIN CANNOT TERMINATE ON NEIGHBORS PROPERTY
5) NEED SMOKIES IN BEDROOMS AND HALLWAY
6) BACK BEDROOM NEED DIFFERENT HARDWARE ON DOORS TO MEET EGRESS
7) NEED GFI PROTECTED RECEPTACLES AT CARPORT
8) LIGHT WITH RECEPTACLE AT BATH NEEDS TO BE GFI PROTECTED OR REMOVE
9) RECEPTACLES AT KITCHEN COUNTER TO BE GFI PROTECTED
10) NEED HIGH/LOW COMBUSTION FOR MECHANICAL ROOM (GAS)