Permit: T09EL00546

Parcel: 13623009B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/13/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BONDING JUMPERS NOT SIZED PROPERLY TO BE SIZED PER NEC 250.102 AND 250.66
05/11/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO ADDRESS SERVICE
2. BOND SERVICE RISER - NEC 250.92
3. EXPOSE GROUND RODS
4. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER - NEC 300.4(F)
5. REMOVE PAINT @ GROUND CONNECTION TO JUNCTION BOX NEC 250.12
6. MAIN BREAKERS IN PANELS TO BE 100 AMP PER PLAN
7. CONNECT GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL CONDUCTOR PER NEC 250.24