Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00546
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BONDING JUMPERS NOT SIZED PROPERLY TO BE SIZED PER NEC 250.102 AND 250.66 |
|
| 05/11/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO ADDRESS SERVICE 2. BOND SERVICE RISER - NEC 250.92 3. EXPOSE GROUND RODS 4. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER - NEC 300.4(F) 5. REMOVE PAINT @ GROUND CONNECTION TO JUNCTION BOX NEC 250.12 6. MAIN BREAKERS IN PANELS TO BE 100 AMP PER PLAN 7. CONNECT GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL CONDUCTOR PER NEC 250.24 |