Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |