Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2009 | ELECTRIC - FINAL | Denied | 1) ALL WIRING BELOW 7' IN LAUNDRY ROOM MUST BE IN CONDUIT OR COVERED WITH SHEETROCK, PLYWOOD, ETC... 2) NEED SMOKE DETECTORS IN EACH BEDROOM AS WELL AS HALLWAY 3' FROM REGISTERS MIN. 3) BOTH BATH LIGHT FIXTURES MUST BE REMOVED OR COVERED WITH GFI BREAKER 4) REPLACE BROKEN OUTLETS IN LIVING ROOM AND KITCHEN 5) KITCHEN OUTLET MUST BE GFI PROTECTED |