Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL00516
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/24/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT USE SHEETMETAL THREAD SCREWS 250.8 2. CONDUCTOR TO BE WHITE ENTIRE LENGTH IN RACEWAY 200.7 3. SECURELY ATTACH RACEWAY SUPPORT TO FENCE |
|
04/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 3/4" PVC CONDUITS |
|
03/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CONDUIT DEPTHS = 18" NON-ROADWAYS & 24" DRIVEWAYS PARKING AREAS PER NEC 300.5 TOP OF CONDUIT TO FINISHED GRADE |