Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED (2) GROUND RODS, REQUIRED ON ALL UPGRADES (6' APART) 2) NEED TO COMPLETE PANEL (I.E. ADRESS AND SERVICE CONDUCTORS FOR TEP TO CONNECT TO MINIMUM 24" OUT OF WEATHER HEAD |