Permit: T09EL00446

Parcel: 138234610


Addresses:

791 W LIGHTSTAR CI


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09EL00446

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
03/04/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING COVERS EXTERIOR GFCI OUTLETS
2) SECURE LIQUID TIGHT 12" FROM BOX CONDENSOR DISCONNECT
3) CONDENSOR OVER FUSED 30 MAX FUSE
4) MISSING FRONT DOOR LIGHT FIXTURE
5) REMOVE FOAM FROM WATER HEATER AND WATER HEATER FLUE VENT
6) MISSING LIGHT FIXTURES THROUGHOUT
7) INSTALL SMOKE ALARMS ALL BEDROOMS AND HALLWAYS